Strap-on Temperature Sensor

Model:EE441
.Analogue, Digital and Passive Outputs
.Easy Installation
.Configurable and Adjustable



The EE441 strap-on sensor measures the temperature (T) on round ducts and pipes and is optimized for heating systems (warm and cold water pipes) or solar collectors.

 

Active Output

Operating temperature 

-40~70°C

Sensing element

Pt1000(class A, DIN EN60751)

Analogue output 

0-10V、4-20Ma

Digital interface

RS485 with max. 32 unit load devices on one bus Modbus RTU or BACnet MS/TP

Accuracy

± 0.3 ℃(@20 ℃)

Supply voltage (Class III) 

15-35 V DC(for RS485 and 0-10 V output)

10 V DC+RL x20mA < V+ < 35V DC

Current demand (typ.) 

analogue(5 mA (DC) / 12 mA (AC))

RS485(3.5 mA (DC) / 12 mA (AC))

Electromagnetic compatibility

EN61326-1、EN61326-2-3

 

 

Passive Output

Operating temperature (contact area)

-40~+110℃

T sensing elements

Pt100 DIN B、Pt1000 DIN B、NTC1.8k、NTC2.2k、NTC10k B3950、NTC10k B3435、KTY81-210、Ni1000 TK6180 DIN B、Ni1000 TK5000 DIN B

Measurement current typ. 

< 1 mA

T-sensor connection

two-wire

 

 

General

Insulation resistance

 > 100 MΩ (@20 °C)

Response time τ63

< 1 min

Enclosure material

polycarbonate, UL94-V0 approved, T-range: -40...+110 °C (-40...+230 °F)

Protection class

IP65 

NEMA 4

Cable gland

M16 x 1.5

UL94-V2

Hose clamp material

stainless steel (corr. 1.4301 / 304) 

Storage temperature

-30℃~70℃

Working and storage humidity

5 ~95 % RH( non condensing)